Setting up the activation and release delays
Table. 8.4. - 145. DI8 card binary input settings
Name
Description
Range
Step
Default
DIx Polarity De nes if binary input status is 1 or 0 when the input is energized.
0:NO
(Normally
open)
1:NC
(Normally
closed)
-
0:NO
DIx
Activation
threshold
In NO mode: measured voltage exceeding this setting activates the input.
In NC mode: measured voltage exceeding this setting deactivates the input.
16.0…
200.0 V
0.1 V
88 V
DIx
Release
threshold
In NO mode: measured voltage below this setting deactivates the input.
In NC mode: measured voltage below this setting activates the input.
10.0…
200.0 V
0.1 V
60V
DIx
Activation
delay
De nes the delay for status change from 0 to 1
0.000…
1800.000 s
0.001
s
0.000 s
DIx Drop-
off time
De nes the delay for status change from 1 to 0
0.000…
1800.000 s
0.001
s
0.000 s
DIx AC
Mode
Adds 30 ms deactivation delay to account for alternating current. Release
threshold parameter is hidden and forced to 10% of set activation
parameter.
0:Disabled
1:Enabled
-
0:Disabled
Digital input activation threshold can be set for each digital input individually by the user. Properly set
activation and release thresholds will result in reliable activation and release of the digital input states.
User settable normal state (normally open/normally closed) de nes if the digital input is considered
activated when the digital input channel is energized.
Figure. 8.4. - 174. Digital input state when energizing and de-energizing the digital input channels.
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd