Figure. 5.4.2. - 70. Simpli ed function block diagram of the NOC function.
Measured input values
Function block uses analog current measurement values. Function block always utilizes peak-to-peak
measurement from samples and by user selection the monitored magnitude can be either fundamental
frequency RMS values, True RMS values from the whole harmonic specter of 32 components or peak
to peak values. -20ms averaged value of the selected magnitude is used for pre-fault data registering.
Table. 5.4.2. - 29. Analogic magnitudes used by the NOC function.
Signal
Description
Time base
IL1PP
Peak-to-peak measurement of phase L1/A current
5 ms
IL2PP
Peak-to-peak measurement of phase L2/B current
5 ms
IL3PP
Peak-to-peak measurement of phase L3/C current
5 ms
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
IL1TRMS
TRMS measurement of phase L1/A current
5 ms
IL2TRMS
TRMS measurement of phase L2/B current
5 ms
IL3TRMS
TRMS measurement of phase L3/C current
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input channel
variations pre-fault condition is presented with 20 ms averaged history value from -20 ms of Start or
Trip event.
General settings
The following general settings de ne the general behavior of the function. These settings are static i.e.
it is not possible change them with setting group switching.
Table. 5.4.2. - 30. General settings of the function
Name
Description
Range
Step
Default
Setting control from
comm bus
Activating this parameter permits changing the pick-up level of the
protection stage via SCADA.
1:Disabled
2:Allowed
-
1:Disabled
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
72