Table. 5.4.9. - 73. Pick-up characteristics setting (SG selectable)
Name
Range
Step
Default
Description
Enable
TT> Alarm
1
0:Disabled
1:Enabled
-
0:Disabled Enabling / Disabling of the Alarm 1 signal and IO
TT> Alarm
1 level
0.0…
150.0%
0.1%
40%
Alarm 1 activation threshold. Default setting is 40%.
Enable
TT> Alarm
2
0:Disabled
1:Enabled
-
0:Disabled Enabling / Disabling of the Alarm 2 signal and IO
TT> Alarm
2 level
0.0…
150.0%
0.1%
40%
Alarm 2 activation threshold. Default setting is 40%.
Enable
TT> Rest
Inhibit
0:Disabled
1:Enabled
-
0:Disabled Enabling / Disabling of the Inhibit signal and IO
TT> Inhibit
level
0.0…
150.0%
0.1%
80%
Inhibit activation threshold. Default setting is 80%.
Enable
TT> Trip
0:Disabled
1:Enabled
-
0:Disabled Enabling / Disabling of the Inhibit signal and IO
TT> Trip
level
0.0…
150.0%
0.1%
100%
Inhibit activation threshold. Default setting is 80%.
TT> Trip
delay
0.000…
3600.000s 0.005s 0.000s
Trip signal additional delay. This delay will prolong the trip signal generation
for the set time. Default setting is 0.000s which will not give added time
delay for the trip signal.
Function blocking
In the blocking element the block signal is checked in the beginning of each program cycle. Blocking
signal is received from the blocking matrix for the function dedicated input. If the blocking signal is not
activated when the pick-up element activates, a Trip signal is generated and the function proceeds to
the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be generated and the
function shall not process the situation further. If Trip function has been activated before blocking signal
it will reset and the release time characteristics are processed as in case of when pick-up signal is
reset.
From blocking of the function a HMI display event as well as time stamped blocking event with
information of the startup current values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software switch signal
when relay common and global testing mode is activated.
User settable variables are binary signals from the system. Blocking signal needs to reach the IED
minimum of 5 ms before the set operating delay has passedfor blocking to be active in time.
Measurements and indications of the function
TOLT function outputs measured process data from following magnitudes:
Table. 5.4.9. - 74. General status codes
Name
Range
Description