Cold
Reset
default
theta
0.0…
150.0%
0.1%
60.0%
Thermal image status in the restart of the function / IED in percentage of used
thermal capacity of the protected object. Default setting is 60% of thermal
capacity used. Also, possible to fully reset thermal element.
This parameter can be used when testing the function to manually set the
current thermal cap to any value.
Table. 5.4.9. - 72. Environmental settings
Name
Range
Step
Default
Description
Object max temp
(tmax = 100%)
0…
500deg
1 deg
90
Maximum allowed temperature for the protected object. Default
setting is +90 degrees and it suits for Celsius range and for PEX
insulated cables
Ambient temp sel
0:Manual
set
1:RTD
-
0:Manual
set
Selection whether xed or measured ambient temperature should be
used for the thermal image biasing.
Man.Amb.Temp.Set 0…
500deg
1deg
15deg
Manual xed ambient temperature setting for the thermal image
biasing. For underground cables commonly is used 15 degrees
Celsius. Setting is visible if Ambient temp sel is set to “Manual set”.
RTD
Amb.Temp.Read
0…
500deg
1deg
15deg
RTD ambient temperature reading for the thermal image biasing.
Setting is visible if Ambient temp sel is set to “RTD”.
Ambient lin. or
curve
0:Linear
est.
1:Set
curve
-
0:Linear
est
Selection of ambient temperature correction either by internally
calculated compensation based into end temperatures or user
settable curve. Default setting is 0:Linear corr, which means internally
calculated correction for ambient temperature.
Temp.reference
(tref) k
amb
=1.0
-60…
500deg
1deg
15deg
Temperature reference setting. In this temperature manufacturer
presumptions apply and the thermal correction factor is 1.00 (rated
temperature). For ground dug cables this is usually 15
̊
C and in air
25
̊
C.
Setting is visible if Ambient lin. or curve is set to
Linear est.
Max ambient temp
0…
500deg
1deg
45deg
Maximum ambient temperature setting. If measured temperature is
more than maximum set temperature the set correction factor for
maximum temperature shall be used. Setting is visible if Ambient lin.
or curve is set to “Linear est.”
k at max amb temp
0.01…
5.00xIn
0.01xIn 1.00xIn
Temperature correction factor for maximum ambient temperature
setting. Setting is visible if Ambient lin. or curve is set to “Linear est.”
Min ambient temp
-60…
500deg
1deg
0deg
Minimum ambient temperature setting. If measured temperature is
less than minimum set temperature the set correction factor for
minimum temperature shall be used. Setting is visible if Ambient lin.
or curve is set to “Linear est.”
k at min amb temp
0.01…
5.00xIn
0.01xIn 1.00xIn
Temperature correction factor for minimum ambient temperature
setting. Setting is visible if Ambient lin. or curve is set to “Linear est.”
Amb.Temp.ref1...10 -50.0…
500.0deg 0.1deg
15deg
Temperature reference points for the user settable ambient
temperature coef cient curve. Setting is visible if Ambient lin. or
curve is set to “Set curve”.
Amb.Temp.k1...k10 0.01…
5.00
1.00
0.01
Coef cient value for the temperature reference point. Coef cient and
temperature reference points must be set as pairs. Setting is visible if
Ambient lin. or curve is set to “Set curve”.
Add curvepoint 3…
10
0:Not
used
1:Used
-
0:Not
used
Selection whether the curve temperature / coef cient pair is in use.
Minimum amount is two pairs to be set for the temperature /
coef cient curve and maximum is ten pairs. If measured temperature
is less than set minimum temperature reference or more than
maximum set temperature reference the used temperature coef cient
shall be the rst or last value in the set curve. Setting is visible if
Ambient lin. or curve is set to “Set curve”.
Operation characteristics
The operating characteristic of the TOLT function is completely controlled by the thermal image. From
the thermal image calculated thermal capacity used value can be set IO controls with Alarm 1, Alarm
2, Inhibit and Trip signals.
AQ-T216
Instruction manual