Figure. 5.4.6. - 78. Retrip and CBFP when selected criteria is current or DO.
In case when the current based protection activates so that either Iset and/or I0Sset current threshold
setting is exceeding the counters for retrip and CBFP start to calculate the set operating time. From the
tripping signal of the primary protection stage the counters for retrip and CBFP start to calculate the
set operating time. The tripping of the primary protection stage is constantly monitored in this
con guration regardless of the current status. The pick-up of CBFP is active until current is not
decreased under the setting limit or the trip signal from primary stage is not reset. In case if either of
these conditions are met until the timers set time rst is issued retrip and if either of the conditions is
active also CBFP will be issued to upstream breaker. If the primary protection function clears the fault
e.g. the circuit breaker operates normally the counters for retrip and CBFP are reset immediately the
current is measured below the threshold settings and the trip signal is reset. This con guration allows
the CBFP to be controlled on current based functions with added security from the current monitoring
of the CBFP function and other function trips can be also included to the CBFP functionality.
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
96