Thermal withstand
25A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
1mA…75A(rms)
Current measurement inaccuracy
0.002xIn…25xIn < ±0.5% or < ±0.6mA
25xIn…375xIn < ±1.0%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.01A)
< ±1.0 ° (I
≤
0.01A)
Burden (50Hz/60Hz)
<0.1VA
Transient overreach
<5%
Terminal block
Solid or stranded wire
Phoenix Contact FRONT 4H-6,35
Maximum wire diameter:
4 mm2
Note: Current measurement accuracy has been veri ed with 50Hz/60Hz.
Amplitude difference is 0.2% -and angle difference 0.5 degrees higher at 16.67Hz and other
frequencies.
9.1.1.2. Frequency measurement
Table. 9.1.1.2. - 148. Frequency measurement accuracy
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2. CPU & Power supply
9.1.2.1. Auxiliary voltage
Table. 9.1.2.1. - 149. Power supply model A
Rated values
Rated auxiliary voltage
85…265V(AC/DC)
Power consumption
< 7W
< 15W
Maximum permitted interrupt time
< 60ms with 110VDC
DC ripple
< 15 %
Terminal block connection
Solid or stranded wire
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2
Table. 9.1.2.1. - 150. Power supply model B
Rated values
AQ-T216
Instruction manual
Version: 2.00