Figure. 5.4.9. - 95. Simpli ed function block diagram of the TOLT function.
Measured input value
For the function block is used analog current measurement values. Function uses the fundamental
frequency magnitude of the current measurement inputs and calculated residual current with residual
current measurement. For residual current measurement can be selected I01 or I02.
Table. 5.4.9. - 69. Analogic magnitudes used by the TOLT function.
Signal
Description
Time base
IL1RMS
Fundamental TRMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental TRMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental TRMS measurement of phase L3/C current
5 ms
RTD
Temperature measurement for the ambient correction
5 ms
Table. 5.4.9. - 70. General settings of the TOLT stage (not SG selectable)
Name
Range
Step
Default
Description
TT> mode
0:Disabled
1:Activated -
0:Disabled Selection of the function is activated or disabled in the con guration. Default
setting 0:Disabled (Not in use).
Temp C or
F deg
0: C
1: F
-
0:C
Selection whether the temperature values of the thermal image and RTD
compensation are shown in Celsius or Fahrenheit degrees.
Table. 5.4.9. - 71. Thermal replica settings.
Name
Range
Step
Default
Description
IN
thermal
cap
current
0.10…
40.00xIn
0.01xIn 1.00xIn
Current for the 100 % thermal capacity to be used (pick-up current in p.u., with
this current t
max
will be achieved in time t x 5). Default setting is 1.00 xIn.
tau h (t
const)
0.1…
500.0min 0.1min
10.0min Time constant setting. This time constant is used for heating of the protected
object.
tau c (t
const)
0.1…
500.0min 0.1min
10.0min Time constant setting. This time constant is used for cooling of the protected
object.
kSF
(service
factor)
0.01…
5.00
0.01
1.00
Service factor which corrects the maximum allowed current value according to
installation etc. conditions which vary from the presumption conditions.
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
118