Secondary Zero sequence current
0.00…
300.0A
0.01A Secondary measurement from calculated zero sequence
current
Table. 5.2.1. - 20. Sequence current angle measurements
Name
Range
Step
Description
Positive sequence current angle
0.00…360.0deg
0.01deg
Calculated positive sequence current angle
Negative sequence current angle
0.00…360.0deg
0.01deg
Calculated negative sequence current angle
Zero sequence current angle
0.00…360.0deg
0.01deg
Calculated zero sequence current angle
Table. 5.2.1. - 21. Harmonic current measurements
Name
Range
Step
Description
IL1 Harmonics
IL1 fund…IL1
31harm
0.00…
1000000.0A
0.01A Per unit, primary and secondary harmonics per component for current
input IL1
IL2 Harmonics
IL2 fund…IL2
31harm
0.00…
1000000.0A
0.01A Per unit, primary and secondary harmonics per component for current
input IL2
IL3 Harmonics
IL3 fund…IL3
31harm
0.00…
1000000.0A
0.01A Per unit, primary and secondary harmonics per component for current
input IL3
I01 Harmonics
I01 fund…I01
31harm
0.00…
1000000.0A
0.01A Per unit, primary and secondary harmonics per component for current
input I01
I02 Harmonics
I02 fund…I02
31harm
0.00…
1000000.0A
0.01A Per unit, primary and secondary harmonics per component for current
input I02
5.2.2. Frequency tracking and scaling
Measurement sampling can be set to frequency tracking mode or xed user given frequency sampling
mode. Bene t of the frequency tracking is that the measurements are in given accuracy range even
when the fundamental frequency of the power system changes.
Table. 5.2.2. - 22. Frequency tracking effect when the fundamental frequency is changing from 6 Hz to 75 Hz.
Measurement error with xed 50Hz sampling frequency when
frequency changes. Constant current of 5A, frequency sweep
from 6 Hz to 75 Hz
Measurement error with frequency tracking when
frequency changes. Constant current of 5A, frequency
sweep from 6 Hz to 75 Hz
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
54