9.1.3.4. mAout & mAin module
Table. 9.1.3.4. - 162. mA output & mA input module technical data
Signals
Output magnitudes
Input magnitudes
4 x mA output signal (DC)
1 x mA input signal (DC)
mA input
Range (hardware)
Range (measurement)
Inaccuracy
0...33 mA
0...24 mA
±0.1 mA
Update cycle
Response time @ 5ms cycle
Update cycle time inaccuracy
5...10000 ms, setting step 5ms
~ 15 ms (13...18ms)
max. +20 ms above set cycle
mA input scaling range
Output scaling range
0...4000 mA
-1000000...1000000, setting step 0.0001
mA output
Inaccuracy @ 0...24 mA
±0.01 mA
Response time @ 5ms cycle [Fixed]
< 5 ms
mA output scaling range
Source signal scaling range
0...24 mA, setting step 0.001mA
-1000000...1000000, setting step 0.0001
9.1.3.5. RTD & mA input module
Table. 9.1.3.5. - 163. RTD & mA input module technical data
Channels 1-8
2/3/4-wire RTD and thermocouple sensors
Pt100 or Pt1000
Type K, Type J, Type T and Type S
Channels 7 & 8 support mA measurement
Measurement range
mA input range
0-33mA
9.1.3.6. RS232 & Serial ber communication module
Table. 9.1.3.6. - 164. RS232 & Serial ber communication module technical data
Ports
RS232
Serial ber (GG/PP/GP/PG)
AQ-T216