Figure. 5.4.12. - 120. Scheme IA1 single-line diagram with AQ-2xx series relays. Settings are for outgoing feeder AQ-200 relays.
The relay supervising the incoming feeder settings are the same as in the rst example. The relays
supervising the busbar and the outgoing feeder should be set up in the following way. Since there are
sensors connected to Zone 2 and 3 start by enabling Zone2 Enabled and Zone3 Enabled. Sensors
connected to S3 are in Zone 2. Enable Zone2 Light 3. Sensor connected to S2 channel is in Zone 3.
Enable Zone3 Light 2.
If any of the channels has pressure sensing sensor included do the enable pressure in same way as
with normal light sensor. If phase overcurrent or residual overcurrent current is needed in tripping
decision those can be enabled in the same way as enabling the light sensors in the zone. When a
current channel is enabled measured current needs to be over the set current limit in addition to light
sensing.
Measured input values
Arc protection uses sample based current measurement. If required number of samples is found over
the setting limit current condition activates. It is possible to use either phase currents or residual
current in the tripping decision.