Figure. 4.5. - 33. Binary Outputs menu.
Binary inputs, Logic Outputs, protection stage status signals (start, trip & blocked etc.) and object
status signals can be connected to output relay or to start- trip- or user con gurable LEDs in
Device IO
matrix
→
IO Matrix
. Connections can be made as latched |x| or non-latched x. Non-latched output is
dis-activated immediately when triggering signal is disabled. Latched signal stays active until the
triggering signal dis-activates and latched function is cleared.
Clearing latched signals is committed at the mimic display by pressing cancel/back key.
Figure. 4.5. - 34. Programmable Control Switch.
Programmable control switches (PCS) are switches that can be used to control signals in mimic
view. These signals can be used in various situations (controlling logic program, function
blocking etc.)
You can give each switch a name and set access level to determine who can control the switch.
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
32