Analog-input scaling
0:Disabled
1:Activated
0:Disabled
Enables mA input.
Scaling curve 1...4
0:Disabled
1:Activated
0:Disabled
Enables scaling curve and mA input measurement.
Curve1...4 input signal
select
0:RTD S1
resistance
…
15:RTD S16
resistance
16:mA In 1 (I card
1)
17:mA In 2 (I card
2)
0:RTD S1
resistance
De nes the category of measurement used for mA input
control.
Input signal lter calculates an average for received mA signal according to set time constant.
Therefore, rapid changes and disturbances like fast spikes are smothered. The Nyquist rate states that
the lter time constant must be at least double the period time of the disturbance process signal. For
example, a value for the lter time constant is 2 seconds for a 1 second period time of a disturbance
oscillation.
Figure. 5.5.4. - 134. First order low pass lter
Curve signal out of range activates “out of range” -alarm that can be used inside logic or with other
relay functions. The signal can be assigned directly to output relay or LED in IO matrix. Out of range
signal is activated when measured mA signal falls below the set input minimum or exceeds the input
maximum limit. Out of range signal is valuable when for example 4…20mA input signal is used.
Figure. 5.5.4. - 135. If in some case the mA input signal is lost, the value will be xed in to the last actual measured cycle value
(value will not go to minimum if it has been something else when signal breaks).