![Arcteq AQ 200 Series Instruction Manual Download Page 272](http://html1.mh-extra.com/html/arcteq/aq-200-series/aq-200-series_instruction-manual_2964929272.webp)
Serial port wavelength
660nm
Cable type
1mm plastic ber
9.1.3.7. Double LC100Mb Ethernet module (Redundant)
Table. 9.1.3.7. - 165. LC 100 Mbps Ethernet communication module technical data
Protocols
Protocols
HSR and PRP
Sync
IEEE1588 (PIP) clock sync
Ports
Quantity of ber ports
2
Communication port C & D
LC ber connector.
Wavelength 1300nm
Con gurable to 10Mbps or 100Mbps
Fiber cable
50/125μm or 62.5/125μm multimode (glass)
9.1.4. Display
Table. 9.1.4. - 166. HMI LCD display technical data
Dimensions and resolution
Number of dots / resolution
320 x 160
Size
84.78mm × 49.90mm
Display
Type of display
LCD
Color
Monochrome
9.2. Functions
9.2.1. Protection functions
9.2.1.1. Non-directional overcurrent (50/51) I>
Table. 9.2.1.1. - 167. Non-directional overcurrent (50/51) technical data
Input signals
Input magnitudes
Phase current fundamental freq RMS
Phase current TRMS
Phase current peak-to-peak
Pick-up
Pick-up current setting
0.10…50.00 x In, setting step 0.0001 x In
0.10…50.00%I
1f
, setting step 0.01 %I
1f
Inaccuracy
-Current
-2
nd
harmonic
±0.5 %I
SET
or ±15 mA (0.10…4.0 x I
SET
)
±1.0 %-unit of 2nd harmonic setting
Operation time
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
AQ-T216
Instruction manual
Version: 2.00
271
© Arcteq Relays Ltd