Inputs for the function are setting parameters and measured and pre-processed current magnitudes.
Function output signals can be used for direct IO controlling and also for user logic programming. The
function registers its operation into 12 last time-stamped registers and also generates general time
stamped ON/OFF events to the common event buffer from each of the two output signal. Time stamp
resolution is 1ms. Function provides also cumulative counters for CTS alarm and BLOCKED events.
Simpli ed function block diagram of CTS functionIn is presented in the following gure .
Figure. 5.6.1. - 137. Simpli ed function block diagram of the CTS function.
Measured input values
Function block uses analog current measurement values. Function uses the fundamental frequency
magnitude of the current measurement inputs and calculated positive and negative sequence currents.
For residual current measurement can be selected: None, I01 fundamental component or I02
fundamental component.
Table. 5.6.1. - 114. Analogic magnitudes used by the CTS function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
I01RMS
Fundamental RMS measurement of residual input I01
5 ms
I02RMS
Fundamental RMS measurement of residual input I02
5 ms
I1
Phase currents positive sequence component
5 ms
I2
Phase currents negative sequence component
5 ms
IL1Ang
Fundamental angle of phase L1/A current
5 ms
AQ-T216
Instruction manual
Version: 2.00
201
© Arcteq Relays Ltd