64
Configuring the Model 1133A
Arbiter protocol, view data using PSCSV in various ways, including Spreadsheet, Real time,
Phasor Vector or Frequency Plot, depending on the data type.
7.10
Configuring Multimode Relays
Configure the four multimode relays using the Configure Relay Parameters window. Connect to
these relays at the rear panel of the 1133A at the location labeled “Contact Outputs.” You may
manually switch relays in two modes: (1) User Schedule, Override and (2) Communications. For
additional detail on relays, see Chapters 3 and 12.
There are seven configuration choices available: Inactive (default), User Schedule No Override,
User Schedule Override, Communications, One Pulse Per Hour, Trigger and KYZ.
To open the Configure Relays window, click the Configure Relays button or select Connection
>
Configure
>
Relay Parameters. Select one of the four Relays to select the mode. In Figure 7.16,
Relay 1 Mode is selected as “User Schedule, No Override.”
Figure 7.16: Configure Relay Parameters
7.10.1
Configuring User Schedule Mode
1. In the User Schedule mode, relays are activated by timed events that are defined by first
selecting the User Schedule button for the specific relay and then selecting “User Schedule”
to specify the times, date, and ON / OFF conditions.
2. Select a relay (e.g. Relay 1 Mode) and select one of the User Schedule modes.
3. Select User Schedule from the left panel at the bottom; if nothing is scheduled, the right
panel will be blank.
4. Click the Add button to add a new schedule to the relay. Click the UTC Date to open
a selection calendar. Select the relay to which it applies and specify whether the relay is
scheduled ON or OFF.