6.2 Menus, Toolbars, Buttons and Windows
37
6.1.4
Power Quality, DNP and Modbus
Poll specific data from the 1133A using either DNP or Modbus, from the two serial ports or Ethernet
port. To configure any port for DNP or Modbus protocol, see Configuring DNP and Modbus in
Sections 7.6 and 7.7. For specific DNP 3.0 and Modbus data codes, see Chapter 13.
6.1.5
Scheduled Data, Relays and KYZ Pulses
The 1133A comes configured with four SPDT Form C, multi-function relays. For configuring these
multifunction relays see “Configuring Multimode Relays” in Section 7.10. If you want to use these
relays for KYZ pulse metering, make sure to order Option 06, KYZ–Rated Solid-State Relays.
6.2
Menus, Toolbars, Buttons and Windows
The PSCSV main screen shown in Figure 6.1 provides access to its many features by assembling
them together according to functional groups called menus, toolbars, function buttons and windows.
Most of the functions are not available until a user is connected to a specific port and logged on
using a specific user account. For information on connecting see “Connecting with the 1133A”
in Section 6.4, for logging on and user accounts see Section 6.4.12 and for 1133A security see
Section 7.14.
Figure 6.1: PSCSV Main Window
6.2.1
Moving and Viewing Features
Move any toolbar and dock it around the main window by selecting and holding one of the toolbar
handles and dragging the toolbar to a preferred location. Use “View” on the main menu to switch
toolbars ON or OFF depending on need and available space.