130
Technical Specifications and Operational Parameters
12.11
IP Address
192.168.000.254
Default value
(other)
Set up by user with PSCSV software.
12.12
Ethernet (Physical) Address
Set at factory
Last 3 pairs of 48 bits (shown in Hex) are same as unit
serial number. Check using STATUS/TIME button (e.g.
for 00-01-B3-BC-61-4E, 00-01-B3 is fixed, BC-61-4E is
the unit serial number, which is 12345678 in decimal).
12.13
Measurement Specifications
Note: Accuracy specifications include all sources of uncertainty. Except as noted, specifications
apply for the full operating range, including temperature (–10
◦
C to +50
◦
C), line voltage, input
range including specified over-range, power factor, input frequency, and drifts over a one-year
calibration interval. Specifications assume synchronization to GNSS and operation in 3-element
mode or in a well-balanced system where imbalance does not degrade accuracy.
Watts, Wh
0.025% of reading, 10% of range or greater and PF
>
0.2
Under Range
0.0025% of range, below 10% of range
Power Factor
0.005% of VA, PF
>
0.2
VA, VAh
Same as W, Wh except no PF effect
VAR, VARh
Same as W, Wh except replace PF with
√
1
−
P F
2
Vrms
0.02% of reading or 0.002% range, whichever is greater
Arms
0.03% of reading or 0.003% range, whichever is greater
V
2
h
0.04% of reading or 0.004% range, whichever is greater
A
2
h
0.06% of reading or 0.006% range, whichever is greater
Phase Angle,
φ
0.01
◦
, phase-to-phase or voltage-to-current, 10% of range
minimum
Power Factor
0.0002
×
sin(
φ
), 10% of range min.
Harmonics
0.05% THD or 5% of reading, whichever is greater
Frequency
<
1 ppm (0.0001%) of reading, 50 or 60 Hz nominal, plus
time base error
System Phase
0.03
◦
plus [time base error
×
360
◦
×
frequency]
System Time
1
µ
s plus time base error
Event Inputs
±
10
µ
s (typical)