5.2 Overview of Command Keys
33
Status, Ethernet; TCP/UDP Port and Physical Address
Press the Status/Time key to view the TCP/UDP values and physical address. To access this
screen, see Section 5.2.5 notes. Configure TCP and UDP values only from PSCSV
−
for details,
see Section 7.3, “Configure Ports
−
Ethernet”. After changing the TCP or UDP values, power
cycle the 1133A for the new values to take effect. In this example, BC-61-4E is the unit serial
number in hexadecimal notation (in decimal it is 12345678).
Figure 5.16: Status, Ethernet; TCP/UDP
Port and Physical Address
Status, Serial Port Parameters
Press the Status/Time key to view the serial port communication settings for SERIAL 1 and
SERIAL 2. See Section 5.2.5 notes to access this screen. To configure serial port settings, see
“Configuring an 1133A Communications Port” in Section 7.2.
Figure 5.17: Status, Serial Port Parameters
5.2.6
Power Key
Press the POWER key successively to view the four power screens. Each screen lists all of the
available power information (kW, PF, kVA and kVAR) for one of the three phases and total (e.g.
A, B, C and T).
Figure 5.18: Power Key
5.2.7
Energy Key
Press the ENERGY key successively to view the four Energy screens. Each screen lists all of the
available energy information (kWh, kVAh, and kVARh) for one of three phases and total (A, B, C
and T).
Figure 5.19: Energy Key