FireFinder
™
Installation Commissioning & Operation
Page 71
IMPORTANT NOTE:
It is strongly recommended that all field programming changes be properly recorded.
Function And Menu
13.2 The Default LCD Display
In its normal state the
FireFinder
™ will display a screen similar to that shown below.
FIREFINDER 15/7/2005 14:00:00
AMPAC
PH: 08 9242 3333
SYSTEM IS NORMAL
Figure 86: The Default LCD Display
This screen can be configured with the servicing company’s name and phone number via a laptop or
modem. The current date, time is set in the Function menu while system status is automatically displayed.
13.3 Accessing Functions and Menus
At Levels 2 and 3 access to the panel Functions are password protected.
A new panel has a pre-programmed password of
2222
for Level 2 and
3333
for Level 3. When the
customer takes control of the panel the password can be changed to suit their requirements.
☞
NOTE:
All menus are provided with screen prompts and a “Quick Reference Guide” ( see Section
24 ) guides the operator through the operation of the FAC .
13.4
Function Menu and Access Levels
Three levels of ACCESS are available. Level 1 has access to MENU only while Password protected Levels
2 and 3 access MENU and FUNCTION as listed below. ( also see the Quick Reference Guide, Section 24 )
Level II:
Allows access to:
•
Date:
Enter the Day, Month and Year (4 digit year).
•
Time:
Enter the hours and minutes (24 hour mode).
•
Day/Night Settings:
Enter the Day / Night ON times and Enable - Disable.
•
Logs:
Fire Alarm, Fault, Isolate, System & Input / Output logs.
•
Tests:
Walk and loop tests.
•
I/O:
Sets the functionality of Input / Output devices.
•
Access:
Password entry to Level 3
Level III:
In addition to the Level I & II facilities, Add, Delete, Delete all passwords and Mode ( Zone /
Sensor ) onsite Programming
.
13.4.1 Forgotten
Passwords
Follow the following process if a password has been forgotten or misplaced;
a.
entering 9999 into the password field;
b.
take note of the 4 digit password number displayed on the screen; then
c.
contact the AMPAC head office and quote the above number;
A temporary password will be issued and a new password can then be programmed into the FACP.
☞
NOTE:
The temporary password becomes invalid if 9999 is entered again or if the panel is re-
powered after 9999 has been entered.
FUNCTION
MENU
From the
DEFAULT DISPLAY
, press
MENU
or
FUNCTION
. The
FUNCTION
menu is password protected (actually a pass-number as it can only contain
numbers) to prevent unauthorised changes to the panel's configuration.
Summary of Contents for SP Series
Page 2: ......
Page 110: ...FireFinder Installation Commissioning Operation Page 104 Notes ...
Page 111: ......