FireFinder
™
Installation Commissioning & Operation
Page 47
9
LCD Screen Format
There are 3 events that can be reported and displayed by
Smart
Terminal
. The types of event are;
1.
Fire
2.
Faults and
3.
Disables.
The types of events are only associated with sensors and detectors hence faults associated with modules,
loops O/C – S/C, power supplies and so forth are not reported on the LCD.
The
Smart
Terminal
has front panel indicators for each type of event. When
Smart
Terminal
is configured not
to report a type of event and that event type is present (and the corresponding front panel indicator is
illuminated on the
Smart
Terminal
), then a standard information screen is displayed on the LCD stating the
system is not normal and the operator should see the FACP.
Alarm
If configured the screen format for reporting loop / sensor / zone fire condition is:
LCD Line Number
Information
1
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
2
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
3
Date and Time of occurrence (DD/MM/YYYY HH:MM:SS)
4
Alarm sequence number ( Device Alarms nnn of nnn)
Fault
If configured the screen format for reporting loop / sensor / zone fault condition is:
LCD Line Number
Information
1
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
2
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
3 Blank
4
Fault sequence number ( Device Fault nnn of nnn)
Note: The fault types only relate to devices.
In the event of a loss of communications, for a period of greater than 15 seconds the
Smart
Terminal
will default to the No Communications screen. The format for this screen is:
LCD Line Number
Information
1
2 No
Communications
3
4
Device Isolate / Disables
If configured the screen format for reporting loop / sensor / zone disable condition is:
LCD Line Number
Information
1
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
2
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
3 Blank
4
Isolate / Disable sequence number ( Device Fault nnn of nnn)
Pre-alarm
If configured the screen format for reporting loop / sensor / zone Pre-alarm condition is:
LCD Line Number
Information
1
Loop address and zone number(Lxx Syyy.zz Zwww)
2
Pre-alarm descriptor (up to 15 characters)
3
Line is left blank
4
Pre-alarm sequence number ( Device Pre-alarms nnn of nnn)