FireFinder
™
Installation Commissioning & Operation
Page 45
Buzzer
The Buzzer is activated under the following conditions and can be silenced by pressing the
Acknowledge (ACK) control locally or on the FACP.
9
Alarm
condition
9
Devices – missing, out of calibration, wrong type, reporting an internal error
9
Loops – short circuit or open circuit
9
Monitored inputs and outputs on loop devices are in fault
9
Sounders – missing, wrong type or reporting an internal error
9
Modules within the panel – missing, wrong type or hardware error
9
Main and / or secondary power supply fault
8.12
Smart
Terminal Indicators
Introduction
The following section details the operation of the front panel indicators on the
Smart
Terminal.
Isolate
ISOLATED
ISOLATE
Indicator is illuminated when one or more device/s or conventional zones are isolated
either at the
Smart
Terminal
or the FACP.
Fault
FAULT
RESET
Indicator is illuminated when there is one or more faults on the system. Faults can be;
Devices – missing, out of calibration, wrong type, reporting an internal error
Loops – short circuit or open circuit
Monitored inputs and outputs on loop devices
Sounders – missing, wrong type or reporting an internal error
Modules within the panel – missing, wrong type or hardware error
Main and secondary supplies
Alarm
ACK
ALARM
General fire alarm indicator. The LED will flash until all alarms have been
acknowledged. Once Acknowledged the LED will remain steady until all alarms have
been cleared by Reset.
Warning System
ISOLATE
WARNING
SYSTEM
Illuminated when the Warning System output has been isolated either at the
Smart
Terminal
or the FACP.
External Bell
ISOLATE
EXTERNAL
BELL
Illuminated when the External Bell output has been isolated either at the
Smart
Terminal
or the FACP.
Power
POWER
Illuminated to show the presence of power. Flashes when mains have
failed
Summary of Contents for SP Series