FireFinder
™
Installation Commissioning & Operation
Page 91
(h)
Alarm zone parameters:
Each alarm zone circuit is within the equipment
manufacturer’s specifications.
(i)
Wire-free alarm zones:
Wire-free actuating device parameters meet the minimum
parameters specified by the manufacturer, including that the receiver responds to
signals from an actuating device for alarm, tamper, low standby power signals and
gives a fault signal when the supervisory signal condition is absent.
(j)
Operation of fault and alarm signals:
Fault and alarm conditions correctly detect and
indicate as the correct. alarm zone, operating other required indicators, and operate
relevant outputs of the CIE.
(k)
Mimic panel:
All mimic panels, annunciators, etc., operate correctly.
(l)
Alarm zone controls:
Alarm test, fault test, isolate and reset facility of each alarm
zone operates correctly.
(m)
Alarm dependency:
Alarm dependency works correctly and does not apply to
devices listed in Clause 3.3 of AS 1670.1.
(n)
CIE response to actuating device operation:
Each actuating device has operated
when tested with a medium suitable for the device type and the alarm has indicated on
the FIP and at the tested device.
(o)
Fault response time:
The response to a fault does not exceed 100 s for each alarm
zone circuit.
(p)
Alarm response time:
At least one detector in each alarm zone has been tested and
the response to the alarm does not exceed 10 s or the period specified when
dependency on more than one alarm signal is used.
(q)
Supervisory signal response time:
At least one supervisory device in each alarm
zone circuit has been tested and the response to the supervisory device does not
exceed 100 s.
(r)
Alarm acknowledgment facility:
Alarm acknowledgement facilities operate in
accordance with the requirements of Clause 3.2 AS 1670.1.
(s)
Occupant warning system
(i) A fault signal is displayed at the CIE when the circuit wiring at the last speaker or
sounder is short or open circuited.
(ii) Each sounder/speaker operates in accordance with the requirements of Clause
3.22 of AS 1670.1 and a record of the sound pressure level has been made.
(t) The external alarm indication is visible from the main approach to the building.
(u)
Manual call points
(i) Each manual call point operates correctly.
(ii) The activation of manual call points do not cause existing detector alarm
indications to be extinguished.
(iii) Manual call points are not subject to alarm dependency.
(v)
Smoke and fire door release:
Each door-release device operates correctly.