FireFinder
™
Installation Commissioning & Operation
Page 96
POWER SUPPLY & BATTERY CALCULATOR
Panel Configuration
Iq Calculation
Iq
Evac
Type
Iq in
mA
Ia in
mA
No Off X mA
= Iq
Basic 1 loop panel
240
EV20
41 650
Basic 2 loop panel
254
Basic 16 Zone panel
360
EV40
140
2500
Extender
1.8
EV60
150
3800
LCD repeater
156.2
EV120
150
8500
LED repeater
27
Evac Module
Interface Modules
Additional 3,5 loops add
40
each
Additional 2,4 loops add
15
each
16 zone
143
16/16 I/O
5
Fire Fan Control
14
32 Zone LED
0
Network I/F
74
Controller I/F
5.1
Valve or Pump Display
3.7
8 Way Bell Monitor
20
Agent Release
29
Loop Devices
XP95 Thermal A / B
0.25
Discovery Thermal C&D
0.5
XP95 Ion
0.28
XP95 Photo
0.34
Discovery Multisensor
0.5
Discovery Photo
0.4
Discovery Ion
0.5
XP95 Short cct isolator
0.11
XP95 I/O module
1.2
XP95 Sounder control
1.9
XP95 MCP
0.35
XP95 Zone Monitor
6
Ampac 3 I/O loop power
2.1
Ampac 3 I/O ext. power
1.5
Ampac SID / SIOD
1.7
Iq
=
Devices activating when the system is in alarm
8 x Relays
60
Bell
30
Other
Ida=
Devices de-activating when the system goes into alarm
Aircon Relays
20
Electric locks
100
Other
Idd=