FireFinder
™
Installation Commissioning & Operation
Page 76
The type of log, number and totals logged, date and time of the ALARM, FAULT, ISOLATE, SYSTEM or
I/O as well as device information will be displayed. The SYSTEM screen displays events and watchdog
activity. From these screens the operator can select two other facilities, they are;
Press
m
PRINT ENTRY
will print out the displayed information if a printer is installed, or
n
SHOW OPTIONS
allows the operator to select how the Logs are viewed
.
Press
m
to
VIEW BY
ENTRY NUMBER
or
n
to
VIEW BY DATE
. In each case the screen
will ask for the appropriate information ( ENTRY NUMBER or DATE ) to be entered before
the selected option will be displayed.
☞
NOTE:
it is possible to scroll through the alarms by using the PREVIOUS and NEXT keys.
15.5 The Function Test Facility
Press
q
TESTS:
prompts the operator to select either the
WALK
or
LOOP
test.
Press
m
WALK TEST;
the operator will be prompted to select either
ZONE
or
SENSOR
test.
Press
m
ZONE WALK TEST MENU;
This screen requires the operator to select a Zone or number of Zones to be tested, that is enter the
Zone number press ENTER or enter the Zone number press TO then the next highest
Zone number to be tested EG. 2 TO 7 then ENTER .
The
TEST
MODE LED
will be illuminated for the duration of the test and the test will run until the
operator
RESETS
the system or the test times out [Time Out = 15 m 3 to 5 seconds].
Press
n
SENSOR
WALK TEST MENU
This screen requires the operator to select a Zone and then a Sensor or number of Sensors
(using the TO key) to be tested then pressing ENTER to start the test.
The
TEST
MODE LED
will be illuminated for the duration of the test and the test will run until the
operator
RESETS
the system or the test times out [Time Out = 15 m 3 to 5 seconds].
Press
n
LOOP TEST
requires the operator to select a
LOOP
for
DIAGNOSTIC TESTING
Entering the LOOP number and pressing ENTER
will initiate the
DIAGNOSTIC TEST
.
☞
NOTE:
The LEDs on the Brigade Board will indicate which leg is being tested
.
The tests displayed are;
➢
TESTING SIDE A
IDENTIFING DEVICES on SIDE A, and
➢
TESTING SIDE B
IDENTIFING DEVICES on SIDE B.
Once the testing is completed the final screen will display the number of devices found and tested
on the LOOP and a Reset is requested to return the system to normal.
☞
NOTE:
If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN
.