10.8 Warning Signs
Description
The warning signs are driven by a 2 wire system and may be configured for single or dual stage operation.
An on-board buzzer provides an audible warning which may be disabled by removing JP3.
External evacuation devices, eg sounders may be connected to TB3 of the input termination board. An
external mute push-button (N/O contacts) may also be connected to Term 3 on the warning sign PCB to
enable the user to silence the internal buzzer and evacuation device. Inserting JP4 disables this function.
Enclosures
The
IP50
is a metal enclosure. The facia surround is fitted by removing the screw on the left hand side of
the enclosure and pulling it away to the left. The facia sign is fitted in place and the tabs bent over to hold it
in place. Two holes in the backpan of the chassis allow for mounting.
The
IP65
ABS enclosure has 10 screws, tightened evenly but not over tightened, hold the facia in place.
Do not over tighten. 4 holes in the backpan allow for mounting.
Specifications:
•
Operational Voltage
28VDC
•
Power Consumption Continuous
At 24VDC 55mA Stage 1
At 24VDC 140mA Stage 2 (100mA Muted)
•
IP Ratings
IP50 ( Dim: 190H x 315W x 73D mm )
IP65 ( Dim: 200H x 295W x 65D mm )
•
Environmental
-10
˚
C to +55
˚
C Dry heat
+40
˚
C @ 0 to 93% Relative Humidity
Installation
1.
Remove the backpan from the enclosure to ensure it is not damaged while mounting the
enclosure.
2.
Bring the cabling into the enclosure by removing the knockouts most appropriate for the
installation.
3.
Mount the enclosure, remount thebackpan, set the configuration and then cable as per the
following diagram.
4.
ENSURE THE AGENT IS ISOLATED
and test from the Agent Release Module.
Cabling
Term 3
(Buzzer Mute)
BUZZER MUTE
Normally Open [ N/O ] Push Button Switch (Optional)
INPUT
Term 4
( Single pair polarity reversing / 2 Stage Input )
Stage 1
0V – 24VDC
Stage 2
24VDC – 0V
Configuration – Jumper Settings
JP 1
(Continuous / Flashing)
JP
2
(Single / Dual Stage)
1-2 Continuous
LED's Permanently ON
1-2 Single Stage
Full sign on for Stage 1&2
2-3 Flashing
(DEFAULT)
LED's flashing at 1.5Hz
2-3 Dual Stage (
DEFAULT)
Half sign on for Stage 1
Full sign on for Stage 2
JP 3
(Enable Buzzer)
JP 4
(Disable External Mute)
1-2 ENABLE BUZZER
(DEFAULT)
Buzzer activates for
both Stage 1 & 2
1-2 EXTERNAL MUTE
(DEFAULT)
Disable external mute for
internal Buzzer
JP 5
( Enable External Evacuation Device ) [
not used
]
1-2 ENABLE EXTERNAL EVACUATION
External evacuation device will activate on Stage 1 & 2
DEVICE
(DEFAULT)
with the tone dependent on the input polarity