FireFinder
™
Installation Commissioning & Operation
Page 26
6.5
Fire Fan Module BRD25FCB
The Fire Fan Module has four ( 4 ) separate fan controls each having an On, Auto and Off function switch
and a set of three (3) monitoring LED’s. The LED’s indicate the status of the equipment eg. Run, Fault or
Stop. The two ( 2 ) arrow head keys are used to step up and / or down through the three ( 3 ) conditions. A
slip in label can also be inserted into the hinged cover for identification purposes.
A loop driven version is also available (159-0105 )
☞
Note#:
As per AS 1668.1 1991, Clause 14.17.4
lettering on any of the slip in labels must be at least
5mm in height.
Quiescent Current:
13.5mA
Slip In
Label
Module & PCB Securing Tabs
( Top & Bottom )
PCB
Cle
ar P
lasti
c C
lip In
La
bel
Clip On
Plastic Surround
( Push down here and pull
out to remove and insert labels )
WINDOWS
WINDOWS
FOR SLIP
IN LABELS
Lettering on slip in
labels must be at
least 5mm in height.
K2 Termination Link
In
Out
Address
Switch
Set to 1
1
2
3
4
ON
C
N
1
C
N
2
CN1: Communications & 27V IN from CN2 off the previous
Front Panel Card or CN20 on the Main Control Board
CN2: Communications & 27V OUT to Next Front Panel Card.
If Unsed the Termination Link Must be Inserted.
Top Module &
PCB Securing Clips
Bottom Module &
PCB Securing Clips
Figure 32: Fire Fan Module Front Panel
Figure 33: Fire Fan Module PCB Layout
6.6
Fan Termination Board BRD25FTB
The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment it controls via
the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable monitoring
of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop conditions of
that equipment. Monitoring is programmed in the Function Menu for a 3, 4 or 5 Wire Start / Stop, Run,
Fault, Stop & Common functions. The inputs are protected by way of resetable transorbs and resistive /
capacitive networks.
Connectors
CN5
Is used for factory programming only and may not be available on all boards.
Terminal Blocks
TB2 – 5
Are used to connect the fan control and monitoring wiring to the board.
SW1
TB4
TB3
TB2
LK1
TB5
EOL Termination
0V
+
27V
POW
E
R
Address SW
FAN 1
FAN 1
STOP
COM
STOP
FLT
RUN
FAN 2
STOP
COM
STOP
FLT
RUN
START
FAN 3
FAN 3
STOP
COM
STOP
FLT
RUN
START
FAN 4
COM
STOP
FLT
RUN
START
FAN 4
STOP
START
FAN 2
CN1
CN2
CN3
CN4
RS485 Control in from CN2 of Previous
Board or CN21 of the Main Control Board
RS485 Control Out to Next Board or Link 1 EOL is Applied
27V In from the Brigade Broard or CN4 of the Previous Board
27V Out to Next Board if Applicable
1 2 3 4
O N
STOP
COM
STOP
FLT
RUN
START
TB 2, 3, 4 or 5
Cabling from FACP
to Plant / Equipment
1 2 3 4 5 6
FAN CONTROL
SOLID STATE OR
RELAY INTERFACE
FAN MONITORING
0V
INPUTS 1, 2 & 3
+24V O/Ps
RUN
STOP, START, RUN = 3 WIRE
STOP, START, RUN,
STOP = 4 WIRE
STOP, START, RUN, STOP,
FAULT = 5 WIRE
Figure 34: Fan Termination Board Layout and Typical I/O Wiring