Battery capacity at end of battery life
=
( Iq x 24 ) + Fc( Ia x 0.5 )
=
( 769ma x 24 ) + 2( 1049ma x 0.5 )
=
1 1050ma
Note:
☞
1,000ma = 1 Amp
= 19.506Ah
New battery capacity requirement
= 19.5
x
1.25
=
24.375
Ah
Rounded up to nearest available
25
Ah
PRIMARY POWER SOURCE CALCULATIONS
Battery Charger Current
Requirement: Battery is charged for 24 hrs. to provide 5Iq + 0.5Ia
=
( 5x Iq ) + Fc( 0.5 x Ia )
=
( 5 x 769 ) + 2( 0.5 x 1049 )
=
3845 + 1050
Ah Requirement
= 4.895Ah
Battery Charging Current Required
= 4.895
24 x e
e is the battery efficiency, 0.8
=
0.26A ( rounded )
Power Supply Requirement
Select the greater of 1 or 2
1.
Ia + non- battery backed ancillary alarm loads
2.
Iq + non – battery backed quiescent loads
If the power supply is used as the charger the current rating of the supply shall be
[(
1
or
2
) + battery charger current ].
List of Compatible Batteries
( tested by SSL to comply with AS 1603 . 4 1987 Appendix G [ valid until June 2002 ] ).
☞
Note 1:
afp
number is the SSL Listing Number.
Note 2:
Types are the Manufacturers and not the suppliers.
Note 3:
Automotive type batteries are not normally suitable for stationary use.
afp - 791
afp - 792
afp - 1220
afp - 1228
Yuasa
NP Series
Power-Sonic
PS Series
Matsushita
LCR Series
B & B
BP Series
NPH1.3-12
NPH2-12
NPH3.2-12
NPH5-12
NPH16-12
NP0.8-12
NP1.2-12
NP1.9-12
NP2.3-12
NP2-12
NP2.6-12
NP4-12
NP7-12
NP12-12
NP24-12
NP24-12B
NP38-12
NP65-12
PS-1208
PS-1212
PS-1219
PS-1232
PS-1240
PS-1270
PS-12120
PS-12180
PS-12240
PS-12330
PS-12400
PS-12650
LCR12V4BP
LC-R125P
LC-RC1217P
LC-R127P
LC-R127R2P
afp - 1221
Matsushita
LCL Series
LC-LA12V33P
Afp - 1222
Matsushita
LCX Series
LC-X1224P9(AP)
LC-X1228P(AP)
LC-X1238P(AP)
LC-X1242P(AP)
LC-X1265P
LC-XA12100P
BP 1.2-12
BP 1.9-12
BP 4 –12
BP 7 –12
BP 12-12
BP 17-12
BP 24-12
BP 40-12
Summary of Contents for SP Series
Page 2: ......
Page 110: ...FireFinder Installation Commissioning Operation Page 104 Notes ...
Page 111: ......