FireFinder
™
Installation Commissioning & Operation
Page 72
14
The Main Menu
The
MAIN MENU
is accessed by pressing MENU.
FUNCTION
MENU
MAIN MENU
0: ALARMS 1:PREALARMS 2: FAULTS
3:ISOLATES 4: STATUS 5:TEST
SELECT NO.
Figure 87: The Main Menu
Pressing the appropriate number on the keypad while in the MAIN MENU the user can view any;
m
FIRE ALARMS
;
n
PRE-ALARMS
,
o
FAULTS
; Pressing
o
brings up a sub-menu from which a more detailed description of the fault
can be displayed. With a Fault present select a field (
m
to
s
) to view details of the fault.
m
Zones
Sensors
n
Loops
o
Modules
p
Power
Supply
q
Brigade
r
Test
Failures
s
Bells
p
ISOLATES
on the system.
If there are no alarms, pre-alarms, faults or isolates, a message, eg. NO ZONES OR SENSORS IN
ALARM, will be displayed for 1 to 2 seconds and then the display will return to the Main menu.
14.1 Status
Menu
q
Is pressed to access the STATUS MENU.
STATUS MENU
0: LOOPS 1: MODULES 2: I/O
3: SYSTEM 4:AVALUES
SELECT NO.
STATUS MENU
0: LOOPS 1: MODULES 2: I/O
3: NETWORK 4: SYSTEM 5:AVALUES
SELECT NO.
FACP WITH NETWORKING
FACP WITHOUT NETWORKING
Figure 88: The Status Menu
From the STATUS MENU the status of system components and settings can be selected and displayed as
listed below. Note that different screens are displayed for a system with and without networking.
Press
m
Loops:
Enter the loop number and the LCD will display its status, eg normal, type of fault etc.
m
Press
to
print all devices on the loops (
Press
RESET to stop printing )
n
Press
to print totals of the loops (
Press
RESET to stop printing )
n
Modules:
Select the type of module, Slave
m
, P/S
n
, Brigade
o
or External LED Mimic
p
and follow the screen prompts to display the status of the selected field.
o
I/O:
The LCD will display the status of an input or output in a panel or on a loop.
m
Press
to display Output status –
m
IN A PANEL or
n
ON A LOOP
n
Press
to display Input status - –
m
IN A PANEL or
n
ON A LOOP
Once the above is selected follow the prompts and enter the;
i)
I/O controller number then the input or output on that controller or,
ii)
loop, sensor and output number on that device.
The LCD will display if it is configured and if so a description of what that input or output does