FireFinder
™
Installation Commissioning & Operation
Page 65
EV40 Cabling
FireFinder
BRIGADE
PSU MON
BOARD
+27VDC
NOTE:
Ensure F7
is 3Amps
1
2
1
2
TB2
WARNING
SYSTEM
MONITORED
TB5
+
-
MIC - OPTIONAL
ORDER SEPARATELY
RED +27V
BLACK 0V
GREY
WHITE
SYSTEM POWER
WARNING SYSTEM
+
-
D0 9 0 P HILIPS
VOLUME CONTROLS
PAU PEV
TB1
PLUG IN VERBAL MESSAGE BOARD
( OPTIONAL ORDER SEPARATELY )
MICRO
TIMER
4321
O N
OFF
M/MAN
NOCF
PA2
CONT
SPEAKER OPEN
(YELLOW)
E V
PA1
AL
COM FLT
- +
TB3
FUSE
3A
TB4
AMP2
AMP1
SPARE
JUMPERS
o o o o o
o o o o o
A B
TB5
SPEAKER SHORT (RED)
CCT FLT
RELAY
ALM
PWR
o o
o o
o o
o o
o
o
o
o
NOTE 2: IF NO SPEAKER MONITORING IS REQUIRED
PLACE A 22K RESISTOR ACROSS TB4
TERMINALS 1 & 2 TO DISABLE OPEN CIRCUIT LED
8 OHM
40W LINE
TRANSFORMER
302-718
30
2-
718
A
14
/8
/0
0
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
100V IN
100V IN
MONITORED SPK OUT
MONITORED SPK OUT
+ 27VDC IN
- 27VDC IN
FAULT
FAULT
GN D
ALARM
AL IND (0v SWITCH)
EV IND (0v SWITCH)
OUT CON (0v SWITCH)
+ 27VDC
G ND
E V
AUTO
PA1
M 1
GN D
M2
PA2
EVACTRON
EV40
STATUS CONTROL
AL
22K
FRONT PANEL
PINK
RED
PINK
BLACK
GREEN
ORANGE
WHITE
BLACK
RED
MIC
C N3
C N2
CN 1
TB2
1 2
3 4
ON
+
-
WARN
P WR
PWR
+
+
-
TERMINATION
BOARD
TB1
CN 1
IN
OUT
ALERT EVAC
MIC2
MIC1
MESSAGE BRD
MOUNTING SOCKETS
NOTE 1: "WARNING SYSTEM" IS A MONITORED FACP O/P. THE EOL
IS ONBOARD THE EV40 AND IS EFFECTIVELY MADE TO BE O/C
(AT TB1) DURING AN EV40 FAULT CONDITION. THIS PRODUCES
THE FAULT INDICATION AT THE FACP
VERBAL
MESSAGE
BOARD
OCCUPANT WARNING SYSTEM
AUTOMATIC
PUBLIC ADDRESS
MANUAL EVACUATION
LINE FAULT
ISOLATED
Figure 78: Typical EV40 Wiring to Control Module and FACP
ON
4
3
2
1
EV
AC
ALERT
30
60
90
12
0
15
0
18
0
210
240
270
30
0
36
0
420
480
540
SECONDS
O N
O N
O N
O N
OFF
OFF
OFF
OFF
EVAC / ALERT = SEQUENCE GOES
STRAIGHT TO EVAC OR ALERT TONES
SW 1 - 4 = ON
SW 1 - 4 = OFF
TIME OUT TABLE
AND EXAMPLE OF
30SECS SETTING
(FACTORY SETTING
"0" SECONDS)
Figure 79: EV40 Time Out Table
Jumper settings
PEV: -
PA + Evac – must be inserted when a selector switch is connected.
PAU:
- PA in Auto – if inserted allows Mic 1 input (hand held microphone) to be used in “Auto”
(with no FACP alarm ) and paging in “Evac” mode.
PA2 CONT:
- PA2 Control – if inserted allows the PA2 input to also switch the Control Output.
M2 1milli volt:
- if inserted enables a 1mV microphone input for Mic 2, not inserted enables the
input for 100mV line level ( background music etc.)
Summary of Contents for SP Series