TROUBLESHOOTING
E-20
Servodriver fault Signalization input: PLC-A input
0.09
Fault
Cause
Troubleshooting
Neither servo-amplifer
display U6
1. Not indicator lights up. Contactor KM1 is
not switched.
Stop SA1 button is not switched, or
interlock switch for machine opening SA2
is not open.
2. Burnet fuse F4 - T10A.
Replace fuse 12.0008.4.664. ATTENTION
- line voltage!
3. Faulty connection of servo driver supply
connector.
Check correct placement - connection of
servo driver supply connector. ATTENTIO -
line voltage!
4. Faulty clamper contact KM1.
Replace clamper 12.0008.4.833.
ATTENTION - line voltage!
5. Faulty servo-amplifier U6.
Replace servo-amplifier. ATTENTION - line
voltage!
6. Faulty filter Z1.
Check circuit, replace filter 06.1500.0.051.
Indicator flashing on
servo-amplifier U6, or
error message shovn
on its display.
1. Fault by servo-amplifier error message
Switch machine off for more than 1 min
and switch it in again. In case servo-
amplifer still shows error, call service for
help.
E-20
Servo driver error Signalization input: PLC-A input
0.09
Fault
Cause
Troubleshooting
Green indicator flashing
on servo-amplifier U6
or display lights up,
error not indicated, still
servo driver does work
correctly
1. Not efficient connection of connector
CN1 and cable with servo-amplifier
Check correct connection - connection of
all servo.amplifier connectors, especially
cable and conector CN1.
2. Faulty setup of servo-driver parameters.
Unless it is possible to check and set up
parameters manually, it is necessary to call
service. (Servo-amplifier replacement.)
3. Faulty input PLC-A 0.09
Check signal on PLC-A input, replace PLC
06.8015.0.001
E-21
Faulty stepper motors Signalization input: PLC-A input
1.01
Fault
Cause
Troubleshooting
No indicator flashing
on stepper motor driver
and CB1condenser
panel
1. Contactor KM1 does not make contact
Emergency stop SA1button not switched,
or interlock switch for machine opening
SA2 is open.
2. Fuse F3 - T10A burnt
Replace fuse 12.0008.4.664
3. Toroi transformer GS3 faulty
Check or replace transformer
12.0010.4.162
Only one green LED on
CB1 condenser panel
is on, none of driver
indicator is on
1. Fuse F5 or F6 - T10A burnt
Replace fuse 12.0008.4.664
2. Faulty contact on KM1contactor
Replace contactor 12.0008.4.833
ATTENTION - Line voltage!
3. Faulty DU1 or DU2 rectifier
Replace rectifier 12.0008.4.770
4. CB1 condenser panel faulty
Replace panel CB1 12.0010.4.134
WARNING
!
When working with line voltage, it is necessary to disconnect the machine from electricity system!
Repairs cn be carried out by an authorized person with electro-technical qualification only!