MEA-100B
12. Troubleshooting
12-3
E07
Message
FULL WAVE
Time of
detection
During welding
Cause of fault
The monitored conduction angle exceeds 175° during operation with
the power supply voltage fluctuation compensation control. This fault
may occur when it occurred for 3 times or more in the multi-cycle
welding.
Note: This fault does not occur when the secondary constant-current
control is selected.
Measures
Check the welding power supply voltage.
Output signal
Outputs the trouble [NG] signal or the caution [CAUTION] signal, and
the hold end [END] signal when the welding sequence is complete.
When the [CAUTION] is selected for Fullwave, the normal end
[GOOD] signal is output, too.
E08
Message
STEP END
Time of
detection
At the end of the welding sequence.
Cause of fault
The stepper-up operation is complete.
Measures
Input the [STEP RESET] signal, reset the stepper count, or change
the stepper number.
Output signal
Outputs the trouble [NG] signal or the caution [CAUTION] signal
together with the hold end [END] signal, the step end [STP/WELD
END] signal and the normal end [GOOD] signal when the welding
sequence is complete.
E09
Message
STEPUP RATE TROUBLE
Time of
detection
When the start signal is accepted.
Cause of fault
The stepper-up current rate exceeds the setting range during the
stepper-up operation.
Measures
Edit the current up rate so that it falls within the setting range.
During the secondary constant-current control, set the current up
rate so that the stepped-up current does not exceed the set
maximum current.
During the power supply voltage fluctuation compensation control,
the current up rate must not exceed 99.9%.
Output signal
Outputs the trouble [NG] signal when the fault arises.
E10
Message
COUNT MEMORY ERROR
Time of
detection
When the power is turned on.
Cause of fault
The count data stored in memory is damaged.
Measures
Memory was erased because period for retaining memory of count
data elapsed over specified period.
The period for retaining the memory of count data is approximately 10
days since the day when a power supply is turned off at latest.
Output signal
Outputs the trouble [NG] signal or the caution [CAUTION] signal
when the fault occurs.