MEA-100B
11. Timing Chart
11-3
SM on the SET2 screen is set to 0 (For the setting of SM, see 9. (2)
)
The welding sequence is halted if input of the start signal is stopped during SQ.
The welding sequence is halted and [E11: CYCLE TROUBLE] is given if input of
the start signal is stopped between W1 and W2 of the welding sequence. (For
the fault code, see
12. Troubleshooting
.)
The welding sequence will continue to the end during HLD, even if input of the
start signal is stopped.
T1: Time required to start weld force after input of the start signal
SM on the SET2 screen is set to 1 (For the setting of SM, see 9. (2)
)
The welding sequence runs to completion, even if input of the start signal is
stopped after starting W1.
T1: Time required to start weld force after input of the start signal
Welding current
SQ
UP1
C O
UP 2
W 2
DWN
W 1
HLD
T1
Weld force signal(output)
[SOL1/SOL2]
OFF
OFF
Start signal(input)
[START(1ST)]
SQ
UP1
CO
W2
DWN
W1
HLD
T1
OFF
OFF
UP2
Welding current
Weld force signal(output)
[SOL1/SOL2]
Start signal(input)
[START(1ST)]