Rockwell Automation Publication 750-UM006C-EN-P - March 2022
75
Configure and Start Up the Drive
Chapter 4
6. On the Motor Data step, enter the Motor Nameplate data. Click Next.
This information is found in the
Prepare for Initial Drive Startup on
table.
7. On the Stop Mode step, enter the desired stop/brake mode along with
the dynamic brake resistor data collected before startup. Click Next.
IMPORTANT
If customer supplied protection is to be used in place of the calculated
resistor thermal protection for the drive, set the [DB ExtPulse Watts] to its
maximum value.