Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
CGCM Unit Configuration
#HAPTER
,OAD3HARE4AB
The Load Share tab is used to configure the unit’s parameters related to the real
power load sharing function of the unit.
•
Full Scale Voltage - Sets the load share output voltage when the generator is
producing rated real power. The tag
LS_FS_V
in the configuration table
stores this value, expressed in volts.
•
Limit - Sets the maximum per unit load share error reported to the host
controller. The tag
LSLimit
in the configuration table stores this value,
expressed in per unit power.
•
Rate - Sets the maximum change in the load share error per CGCM unit
update cycle. The tag
LSRate
in the configuration table stores this value,
expressed in seconds per rated watts.
Related Parameters
•
GenRated_W
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......