Detailed CGCM Unit Tag Descriptions
'ENERATOR/VERVOLTAGE/UTPUTSFROMTHE#'#-5NIT
•
Ovr_V_Flt
– This tag is used to communicate the occurrence of an
Over-voltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
)NPUTSTOTHE#'#-5NIT
•
Undr_V_FltOutEn -
When this tag is a 1 in the configuration, and an
Under-voltage Fault occurs (as defined by the Undr_V_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-voltage Condition has no effect on the Fault Relay.
•
Undr_V_Setpt -
This tag configures the generator under-voltage setpoint
that the CGCM unit uses to recognize an under-voltage condition. When
the condition occurs, the CGCM unit starts timing toward a trip.
•
Undr_V_TimeDly -
This setting establishes the time to trip the unit once
the generator Under-voltage Setpoint has been exceeded.
•
EngineIdle –
Setting this tag to 1 enables Soft Start mode and disables the
under-frequency, under-voltage, and Loss of PMG protections until the
generator is at rated speed.
'ENERATOR5NDERVOLTAGE/UTPUTSFROMTHE#'#-5NIT
•
Undr_V_Flt -
This tag is used to communicate the occurrence of an
Under-voltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
,OSSOF3ENSING)NPUTSTOTHE#'#-5NIT
•
LossSensingFltOutEn -
When this tag is a 1 in the configuration, and a
Loss of Sensing Fault occurs the Fault Relay is energized. When this tag is a
0 in the configuration, a Loss of Sensing Condition has no effect on the
Fault Relay.
,OSSOF3ENSING/UTPUTSFROMTHE#'#-5NIT
•
LossSensingFlt
- This tag is used to communicate the occurrence of a Loss
of Sensing Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......