Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
#HAPTER
Troubleshooting
0ROTECTION
4ABLE0ROTECTION
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
Loss of excitation current (40)
Wiring error
Check excitation output wiring
Correct wiring as required
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
Over-excitation voltage (59F)
Wiring error
Check excitation output wiring
Correct wiring as required
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
OEL limit exceeded
Check OEL operation
Correct as required
Generator over-voltage (59)
Rapid loss of large load
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
Generator under-voltage (27)
Over load
Wiring error
Check VT wiring. See Voltage
metering trouble shooting
Correct wiring as required
Loss of sensing (60FL)
Fuse open
Check VT fuses
Replace as required
Wiring error
Check for open connections and
phase rotation reversal
Correct wiring as required
Loss of permanent magnet
generator (PMG/Excitation power)
(27)
Supply circuit breaker trip/fuse open Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Correct/replace PMG input
protection as required
Wiring error
Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Correct wiring as required
PMG failure
Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Repair as required
Incorrect configuration
Check single-phase versus 3-phase
selection
Correct as required
Reverse var (40Q)
Under-excitation
Check UEL configuration if required,
Correct as required
Incorrect operating mode selected
Check selected operating mode for
operating requirements
Select as appropriate
Over-frequency (81O)
Governor error
Correct as required
Under-frequency (81U)
Governor error
Correct as required
Reverse power (32R)
Governor error
Correct as required
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......