
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
#HAPTER
CGCM Unit Operation
To activate droop:
•
the metering CTs and generator VTs must be properly connected and
configured.
•
the desired droop setpoint must be written to the
V_DroopSetpt
tag.
•
excitation enabled (tag
SoftwareExcEn
= 1).
•
remote Excitation Enable On (discrete input).
•
the CGCM unit must be in AVR mode (tag
AVR_FCR_Select
= 0).
•
droop must be enabled (
V_DroopEn
tag = 1).
•
droop must be selected (
Droop_CCC_Select
tag = 0).
•
automatic reactive power control must be disabled (tag
PF_VAR_En
= 0).
#ROSSCURRENT#OMPENSATION
Cross-current compensation (reactive differential compensation) is a method of
connecting multiple generators in parallel to share reactive load. Cross-current
compensation requires the connection of an additional CT into the cross-current
compensation input. The CGCM unit operates in a stand-alone application
without the cross-current inputs connected.
The cross-current compensation method of reactive load sharing is possible with
other controllers of similar type. Cross-current compensation monitors the ID
current, V GEN A, and V GEN C inputs to adjust the excitation level. A gain
adjustment is provided to allow tuning of the cross current control. Cross-current
compensation is configured and controlled by using the software interface to the
Logix controller.
To activate cross-current compensation:
•
the generators must be connected in parallel.
•
the cross-current CT and generator VTs must be properly connected.
•
the desired cross-current gain must be written to the
CrossCurrentGain
tag.
•
excitation enabled (tag
SoftwareExcEn
= 1).
•
remote Excitation Enable On (discrete input).
•
the CGCM unit must be in AVR mode
(tag
AVR_FCR Select
= 0).
•
droop must be enabled (
V_DroopEn
tag = 1).
•
cross-current compensation must be selected (
Droop_CCC_Select
tag
= 1) (and
KVAR_LS_En
tag = 1 for firmware rev. 2.
x
).
When cross-current compensation is disabled or control power is removed from
the unit, the cross-current input terminals ID(+) and ID(-) are internally
connected together through a very small impedance.
(1)
(1) For series B devices, the input terminals are not connected together when control power is removed.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......