Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
#HAPTER
Troubleshooting
#OMMUNICATION
The ControlNet Network Status indicators indicate the state of the ControlNet
network connected to the BNC connectors. If more than one state is present, the
status indicators always reflect the highest priority status present on the network.
The following tables describe the status indicator states and the priority of each
status indicator.
4ABLE#ONTROL.ET!AND#ONTROL.ET"3TATUS3ERIES#ANDEARLIERUNITS
3TATUS)NDICATOR
3TATE
0RIORITY
(OWTO6IEW
#AUSE
Both steady off
1 (highest)
View together
Reset or no power
Both steady red
2
Failed to link interface to
ControlNet network
Alternating red and
green
3
Self testing
Alternating red
4
Bad node configuration (such as
duplicate ControlNet network
address)
Steady off
5
View independently
Channel disabled or not supported
Flashing red and green
6
Invalid link configuration
Flashing red
7
Link fault or no frames received
Flashing green
8
Temporary channel error or listen
only
Steady green
9 (lowest)
Normal operation
4)0
A test sequence is performed on this status indicator during startup.
4ABLE.ETWORK3TATUS)NDICATOR!" 3ERIES$UNITS
3TATUS)NDICATOR
3TATUS)NDICATOR3TATE $ESCRIPTION
A and B
Off
Not online/No power
Flashing Red (1 Hz)
Incorrect node configuration, duplicated MAC ID
Alternating Red/Green
Self test of bus controller
Red
Fatal event or faulty unit
A or B
Off
Channel is disabled
Alternating Red/Green
Invalid link cofiguration
Flashing Green (1 Hz)
Temporary errors (node self corrects) or node is not
configured to go online
Green
Normal operation
Flashing Red (1 Hz)
Media fault or no other nodes on the network
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......