Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
Detailed CGCM Unit Tag Descriptions
!PPENDIX
%
,OSSOF%XCITATION/UTPUTSFROMTHE#'#-5NIT
•
LossExcFlt
- This tag is used to communicate the occurrence of a Loss of
Excitation Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
3HORTED%XCITATION/UTPUTFROMTHE#'#-5NIT
•
Spare2
- Indicates when the excitation output short circuit protection is
active. When this tag is a 1, it indicates that a shorted output exists and the
excitation current output has been clamped to a very low level. The tag is
reset by either setting the tag SoftwareExcEN = 0 or by cycling the control
power to the CGCM unit.
/VEREXCITATION6OLTAGE)NPUTSTOTHE#'#-5NIT
•
OvrExcFltOutEn -
When this tag is a 1 in the configuration, and an
Over-excitation Fault occurs (as defined by the OvrExcV_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Over-excitation Condition has no effect on the Fault Relay.
•
OvrExcV_Setpt -
This tag configures the over-excitation voltage setpoint
that the CGCM unit uses to recognize when an over-excitation condition
is present. When the condition occurs, the CGCM unit starts timing
toward a trip based on the Over-excitation Time Delay.
•
OvrExcV_TimeDly -
This tag configures the time to trip the unit once the
over-excitation voltage setpoint has been exceeded.
/VEREXCITATION6OLTAGE/UTPUTSFROMTHE#'#-5NIT
•
OvrExcFlt
- This tag is used to communicate the occurrence of an
Over-excitation Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
'ENERATOR/VERVOLTAGE)NPUTSTOTHE#'#-5NIT
•
Ovr_V_FltOutEn
– When this tag is a 1 in the configuration, and an
Over-voltage Fault occurs (as defined by the Ovr_V_Setpt tag), the Fault
Relay is energized. When this tag is a 0 in the configuration, an
Over-voltage Condition has no effect on the Fault Relay.
•
Ovr_V_Setpt
– This tag configures the generator over-voltage setpoint
that the CGCM unit recognizes an over-voltage condition is present and
starts timing to trip based on the Over-voltage Time Delay.
•
Ovr_V_TimeDly
- This tag configures the time to shutdown the unit
once the generator Over-voltage Setpoint has been exceeded.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......