
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
CGCM Unit Operation
#HAPTER
!UXILIARY)NPUT2EGULATION!DJUSTMENT
The auxiliary input provides a means to remotely adjust the regulation point of
the generator. This analog voltage (-10…10V DC) input signal changes the
setpoint of the selected operating mode by one percent of the applicable rated
value for each volt applied (positive or negative), multiplied by the auxiliary gain
setting for AVR/FCR or VAR/PF.
Refer to
Chapter 4
for more information.
Auxiliary input gain settings range from -99…99. If the gains are set to zero, the
auxiliary input is inactive.
A typical use for this input is with a Power System Stabilizer where adjusting the
regulation point of the generator can increase system stability during power
system kW swings.
,INEDROP#OMPENSATION
Line-drop compensation adjusts generator voltage proportional to generator
load. Line-drop compensation can be used to maintain voltage at a load that is at
a distance from the generator. Generator output reactive current is used to
increase the generator voltage with increasing load, based on the user
configurable line-drop compensation factor. Line-drop compensation is
adjustable from 0…10% of the voltage setpoint in 0.1% steps, which represents
the percent voltage change at rated generator current. Line-drop compensation
cannot be used with droop or cross-current compensation.
0OWER&ACTOR2EGULATION-ODE0&
In PF mode, the CGCM unit controls field excitation current output to maintain
the commanded power factor setpoint. The CGCM unit uses the measured
generator voltages and currents to calculate power factor. The PF feedback loop
includes adjustable proportional and integral gains. To activate PF mode:
•
the metering CTs and VTs must be properly connected and configured.
•
the PF mode gains must be set.
•
the desired power factor setpoint must be written to the
PFSetpt
tag.
•
excitation enabled (tag
SoftwareExcEn
= 1).
•
remote Excitation Enable On (discrete input).
•
the CGCM unit must be in AVR mode (tag
AVR_FCR_Select
= 0).
•
droop must be enabled (
V_DroopEn
tag = 1).
•
droop must be selected (
Droop_CCC_Select
tag = 0).
•
automatic reactive power control must be enabled (tag
PF_VAR_En
= 1).
•
power factor control must be selected (tag
PF_VAR_Select
= 0).
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......