Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
!PPENDIX%
Detailed CGCM Unit Tag Descriptions
$EFINITE4IME/VERFREQUENCY/UTPUTSFROMTHE#'#-5NIT
•
OvrFreqFlt
- This tag is used to communicate the occurrence of an
Over-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
$EFINITE4IME5NDERFREQUENCY)NPUTSTOTHE#'#-5NIT
•
UndrFreqFltOutEn
- When this tag is a 1 in the configuration, and an
Under-frequency Fault occurs (as defined by the UndrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-frequency Condition has no effect on the Fault Relay.
•
UndrFreqSetpt
- This tag configures the generator under-frequency
setpoint at which the CGCM unit recognizes an under-frequency
condition is present and starts timing to trip based on the
Under-frequency Time Delay.
•
UndrFreqTimeDly
- This tag configures the time to
shutdown/annunciate once the generator Under-frequency Setpoint has
been exceeded.
•
EngineIdle –
Setting this tag to 1 disables the under-frequency,
under-voltage and Loss of PMG protections until the generator is at rated
speed.
$EFINITE4IME5NDERFREQUENCY/UTPUTSFROM#'#-
•
UndrFreqFlt
- This tag is used to communicate the occurrence of an
Under-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
2EVERSE0OWER0ROTECTION)NPUTSTOTHE#'#-5NIT
•
RevPwrFltOutEn
- When this tag is a 1 in the configuration, and a
Reverse Power Fault occurs (as defined by the Rev_kW_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, a
Reverse Power Condition has no effect on the Fault Relay.
•
Rev_kW_Setpt
- This tag configures the generator reverse kW setpoint at
which the CGCM unit recognizes a reverse power condition is present
and starts timing to trip based on the Reverse kW fault Delay setting.
•
Rev_kW_TimeDly
- This tag configures the time to
shutdown/annunciate once the generator reverse kW setpoint has been
exceeded.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......