Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
Troubleshooting
#HAPTER
VARs do not share at all and when a
voltage adjust is made, reactive
power transfers to/ from the
machine
Cross current mode is not
enabled/selected
Check
$ROOP?###4?3ELECT
tag
If not active, check/correct logic for
mode selection
Wiring error
Measure voltage at ID+/- terminal
and adjust reactive power/voltage
Correct wiring as required if voltage
signal from CCCT circuit is not
observed
Gain mis-adjustment
Check CCCT Gain
Correct as required
VARs transfer opposite from one
generator to another
CT polarity or differential circuit
wiring error
Verify CT polarity on each generator
by disconnecting differential circuit
and operating on cross-current
control
Correct CT polarity and differential
circuit wiring as needed
VARs share but are unstable
Gain mis-adjustment
Check CCCT Gain
Correct as required
4ABLE#OMPENSATION-ODES#ROSS#URRENT
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
4ABLE#OMPENSATION-ODES,INE$ROP
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
Voltage does not change with
changes in reactive load while not
connected to the grid
Line Drop not active
Check tag
,INE$ROP#OMP
If not active, check/correct logic for
mode selection
Metering error
See Metering troubleshooting
See Metering troubleshooting
Voltage is unstable
AVR Gains misadjusted
Check voltage stability when
operating isolated from load and if
possible in constant voltage control
Calculate/correct AVR gains if
required
Metering error
See Metering troubleshooting
See Metering troubleshooting
4ABLE,IMITING-ODES5%,
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
VARs absorbed exceed the
programmed UEL limit (UEL does not
limit/activate)
UEL not enabled
Check tag
5%,?%N
and
configuration
Correct logic or configuration as
required
UEL Gain misadjusted
Force into UEL
Adjust gains as required
UEL not configured
Check UEL curve intercepts against
reactive capability curve
Correct as required
Metering error
See Metering troubleshooting
See Metering troubleshooting
Excitation is unstable when UEL is
active
UEL Gain misadjusted
Force into UEL
Adjust gains as required
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......