Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
#HAPTER
CGCM Unit Configuration
5%,4AB
The UEL tab is used to configure the unit’s settings related to operation of the
Under-excitation Limiting (UEL) function. The values entered in this tab
establish break points in a piecewise linear curve that defines the characteristic
curve for this function. See the generator manufacturer’s data for the proper
setting information.
Refer to
Chapter 3
for more information on the operation of the UEL function.
•
Under-excitation Limiting Enable – Select this check box to enable
over-excitation limiting. Tag
UEL_En
in the configuration table stores
this parameter. In addition to selecting the check box, which sets the
UEL_En
tag in the configuration table, the
UEL_En
tag in the Output
(Scheduled Write) Data table must also be set to enable this function. In
Series B deices with firmware revision 3.3 or earlier, the UEL limiter
operates if either the enable box is checked or the
UEL_En
tag in the
Output (Scheduled Write) Data table is set.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......