4ABLE2EACTIVE0OWER#ONTROL0&
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
Power Factor not at PF setpoint
PF not enabled
Check input tag
0&?%NED
If not enabled, select appropriate
modes of operation to enable PF
mode
Gain misadjusted
Observe response of PF to changes
in PF setpoint
If a response is slow, increase gain
Diode failure
Use diode monitor if previously
configured or measure/check diodes
Replace as required
Excitation limiting active
Check UEL/OEL active input
Correct UEL/OEL configuration or
change operating point
Power Factor unstable/erratic
Gain misadjusted
Observe response of PF to changes
in PF setpoint
Adjust until a stable response is
observed
Wiring Error
Check stability in other control mode
such as Droop
If stable in other mode, see above.
Otherwise, check field output wiring
and VT/CT input wiring
4ABLE2EACTIVE0OWER#ONTROL6!2
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
VARs not at VAR setpoint
VAR not enabled
Check input tag
6!2?%NED
If not enabled, select appropriate
modes of operation to enable VAR
mode
Gain misadjusted
Observe response of VAR to
changes in VAR setpoint
If a response is slow, increase gain
Diode failure
Use diode monitor if previously
configured or measure/check diodes
Replace as required
Excitation limiting active
Check UEL/OEL active input
Correct UEL/OEL configuration or
change operating point
VARs unstable/erratic
Gain misadjusted
Observe response of VAR to
changes in VAR setpoint
Adjust until a stable response is
observed
Wiring Error
Check stability in other control mode
such as Droop
If stable in other mode, see above.
Otherwise, check field output wiring
and VT/CT input wiring
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......