Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
!PPENDIX%
Detailed CGCM Unit Tag Descriptions
•
BusA_PhOffset
- This tag configures a phase angle added to the measured
bus A phase angle. It is used to compensate for phase shift across sensing
transformers.
•
BusA_V_Scaler
- This tag configures a multiplier by which the measured
bus A voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.
•
BusB_PhOffset
- This tag configures a phase angle added to the measured
bus B phase angle. It is used to compensate for phase shift across sensing
transformers.
•
BusB_V_Scaler
- This tag configures a multiplier by which the measured
bus B voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.
•
BusA_B_Select
– This tag selects which reference bus the CGCM unit
attempts to synchronize to.
•
V_Match
Gain-This tag sets the Proportional Gain parameter for Voltage
Matching mode
3YNCHRONIZING/UTPUTSFROMTHE#'#-5NIT
•
SyncDeadBus
- This tag indicates all conditions have been to allow a
DeadBus synchronization
•
AutoSync
– This tag follows the AutoSyncEn tag setting in the Scheduled
Write tag.
•
CheckSync
- This tag follows the CheckSyncEn tag setting in the
Scheduled Write tag.
•
PermissiveSync
- This tag follows the PermissiveSyncEn tag setting in the
Scheduled Write tag.
•
SyncFailure
– This tag indicates that the synchronization attempt failed.
•
UndefinedSyncMode
– This tag indicates that a synchronization was
initiated when none of the synchronization modes were asserted.
•
SyncModeConflict
– This tag indicates that more than one
Synchronization mode was selected.
•
BusRot_ABC_ACB
– This tag reports the rotation sequence of the
reference bus in three phase metering. In single phase metering, these bits
reflect the configuration value.
•
GenRot_ABC_ACB
– This tag reports the rotation sequence of the
generator bus in three phase metering. In single phase metering, these bits
reflect the configuration value.
•
PhRotMatch
– This tag reports that the phase rotation between the two
busses to be synchronized matches, and is acceptable for synchronizing.
•
V_Match
- This tag reports that the voltage difference between the two
busses is within the configured acceptable range.
•
FreqMatch
- This tag reports that the frequency difference between the
two busses is within the configured acceptable range.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......