CGCM Unit Startup
/VEREXCITATION,IMITING/%, /PERATION
Perform this test with the generator operating unloaded in Constant Speed mode
and constant voltage AVR mode.
Follow these steps to test the OEL operation.
1.
Enable the OEL function.
2.
Determine the field current required to reach 105% of the rated generator
voltage.
3.
Set the offline OEL high and low setpoints for a value equal to the field
current determined above.
4.
Set the voltage setpoint to rated generator voltage.
5.
Enable excitation.
6.
Set the voltage setpoint to 110% of the rated output.
7.
Verify that the generator maximum voltage remains at approximately
105% and that the OEL Active tag = 1.
8.
Observe the response of the excitation current reported by the CGCM
unit.
9.
Adjust the OEL gains as required to obtain the desired stable response.
10.
Return the AVR setpoint to the rated output level.
11.
Return the OEL settings to the values determined for the application.
$IODE-ONITOR
Perform this test with the generator operating in any mode.
Follow these steps to test the Diode Monitor operation.
1.
Input the number of main poles and exciter poles.
2.
Determine the normal percent ripple by observing the ExcRipple tag value.
3.
Find the highest percent ripple while operating the generator and prime
mover through the normal operating range.
4.
Set the Open Diode Level to a value that is three times the highest normal
percent ripple found above.
The multiplier can be varied from 2…5 to adjust the trip margin. Reducing
the multiplier could result in nuisance EDM open diode indications.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......