PhMatch
- This tag reports that the phase difference between the two
busses is within the configured acceptable range.
•
V_MatchErr
– This tag reports the percentage difference in voltage
between the two busses to be synchronized.
•
FreqMatchErr
– This tag reports the difference in frequency between the
two busses to be synchronized.
•
PhMatchErr
– This tag reports the phase difference between the two
busses to be synchronized.
•
CloseBusA_Brkr
– When this tag is 1, it indicates that synchronization
has reached a status where it is acceptable to close the breaker to Bus A.
•
CloseBusB_Brkr
– When this tag is 1, it indicates that synchronization
has reached a status where it is acceptable to close the breaker to Bus B.
•
Raise_V
– This tag indicates to the host Logix controller that the
synchronizing bus has a lower voltage level than that of the reference bus.
•
Lower_V –
This tag indicates to the host Logix controller that the
synchronizing bus has a lower voltage level than that of the reference bus.
•
Raise_Freq -
This tag indicates to the host Logix controller that the
synchronizing bus is producing voltage at a frequency lower than that of
the reference bus.
•
Lower_Freq -
This tag indicates to the host Logix controller that the
synchronizing bus is producing voltage at a frequency higher than that of
the reference bus
•
Raise_Ph -
This tag indicates to the host Logix controller that the
synchronizing bus is producing a voltage that is between 0 and 180 degrees
behind the reference bus.
•
Lower_Ph -
This tag indicates to the host Logix controller that the
synchronizing bus is producing a voltage that is between 0 and 180 degrees
ahead of the reference bus.
•
ActiveBusA_B
– This tag provides feedback as to which reference bus is
being monitored.
,OAD3HARING
This section describes the load sharing inputs and outputs for the CGCM unit.
,OAD3HARING)NPUTSTOTHE#'#-5NIT
•
kVAR_LS_BridgeEn
– This tag is reserved for future use.
•
kVAR_LS_En
– This tag is reserved for future use: must be set to 1 in
conjunction with
kW-LS-EN tag in Rev. 2.x.
•
kW_LS_BridgeEn
– When this tag is set to 1, the CGCM unit uses the
value of kw_AnalogTargetPUValue as the kW Load Share setpoint to
provide appropriate bias to the analog units connected to the LS lines.
•
kW_LS
-
EN
-When this tag is set to 1 the CGCM unit enables the
kilowatt load share function.
Summary of Contents for 1407-CGCM
Page 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Page 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Page 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Page 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Page 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Page 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Page 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Page 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Page 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Page 251: ......