Avoid short circuiting batteries. Short circuit the batteries can damage you
and your environment!
Battery terminal may rise up to 450 Vdc!
1. Switch “CB4”breaker OFF on UPS.
2. If there is breaker on battery cabinet, Switch it “OFF” .
3. Remove the fuse on battery cabinet.
4. Remove battery fuse on UPS.
5. Make sure of serial and parallel connections of external battery packs are correct.
6. Connect the cable to terminals of two neutral "N (battery neutral)" , one "+Battery" and one "-
Battery" respectively.
7. Connect four cables that come from UPS to terminals on battery cabinet or in battery room
according to external battery connection diagram below. As follows:
N(UPS)
-----
Positive Battery Group "-" terminal
N(UPS)
-----
Negative Battery Group "+" terminal
“+ BATTERY”
-----
Positive Battery Group “+“ Terminal
“ -BATTERY”
-----
Negative Battery Group "-" Terminal
8. Make sure that the polarities are connected correctly by checking battery connections for the
last time.
9. Replace battery fuse on UPS.
10. Replace battery fuse on battery cabinet.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...