58
58
Input and output of more than one UPS are connected to each other; but definitely each battery
group is different from another, batteries cannot be used in common. The following points
should be considered while placement of UPS in parallel system and their electrical connections
are made:
The UPSs which are connected in parallel must be from the same series and must have
the same rated power.
Devices must be running on the same firmware, if not, old firmware must be updated.
Devices must be located as close possible as to each other (max. 6 x 110 cm paralleling
cables.)
Each device must have its own ground cable.
UPS must be connected in parallel on the distribution panel an phases must be connected
correctly.
(U
1
-U
2
-…-U
N
), (V
1
-V
2
-…-V
N
), (W
1
-W
2
-…-W
N
).
Each UPS must have their own battery set, batteries cannot be used for more than one
device at the same time.
Power input and output cables from the device to the distribution board must be equal in
length and cross section in order to proceed equal current sharing.
3.2.1 Parallel Settings
3.2.1.1 10-15-20 KVA;
Connect the parallel cable as shown in figure below. Only use the cables provided by AEC.
Software settings on the user panel should be made by authorized personnel.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...