62
62
3.2.2 Parallel Connection Procedure
Please read the following instructions before you use the devices in parallel mode.
3.2.2.1 Check if the devices can be used in parallel mode.
1.
Be sure that all devices are from the same series and rated the same power.
2.
Go to the
version
screen using menu keys, and check if all devices have the same
firmware.
Main screen > Setup > Version
3.2.2.2
Check the positioning of the devices.
Keep the devices as close to each other as possible. The distance between must not exceed 1
meters.
3.2.2.3
Making the electrical connections
1.
Make sure that the devices are turned OFF and have been kept off for at least 5 minutes
before you make any electrical connections.
2.
Connect the devices in parallel through the electrical panel. Refer to parallel connection
example (UDD-SD-40E) for detailed connection drawing. Connect each device to
ground using separate cables.
3.
Connect each device to ground using separate cables.
4.
Make sure that the phases are in the right order.
(U
1
-U
2
-…-U
N
), (V
1
-V
2
-…-V
N
), (W
1
-W
2
-
…-W
N
).
5.
Check the connections using a multimeter in diode mode;
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...